Three Phase Low Voltage Shunt Power Capacitor
Self healing low voltage shunt power capacitor was used in 50HZ and 60HZ power system it mainly improve power factor,reduce reactive power loss,improve voltage quality. Excavate transformer quantity and so on. It is best saving power products which company strong recommended and work.
Standard : IEC 60831-2014
Structure features
Taking cylinder aluminum case.
Immerse liquid: no social effects of pollution dielectric oil.
Inseting press detaching equipment and discharge electric resister
Capacitor core is healing good quality metallized film.
Capacitor top is anti touching electric terminal block.
Bottom is M12 or M16 install ground bolt.
Three phase capacitor is inside △ connection way.
Rated voltage:230VAC,250VAC,400VAC,415VAC, 450VAC, 525VAC,other special voltage please notice it.
Rated capacity:1~50kvar
Rated frequency:50HZ or 60HZ
Capacity tolerance:-5~+10%
Loss Angle Tangent(Power Frequency Rated Voltage):tgδ≤0.01 at 20°C
Anti voltage:between two pole 2.15 times rated voltage is 10s,between two pole 3kv please choose highest value 10s,there is noperpetuity puncture and Flash over
Max permit over voltage:1.1times rated voltage,the high permit over voltage is not more than 8 hours within 24 hours.1.15 times rated voltage,it is not more than 30 minutes within 24 hours,1.2 times rated voltage it is not more than 5 minutes,1.3 times rated voltage,it would not more than 1 minute.
Max permit over current:it is permit that the over current is not more than 1.3 times rated current,interim over current it should consider over voltage,capacity positive tolerance and harmonic effect. Interim over current is not more than 1.43 times rated current.
Discharge property:the left voltage will reduce from √2 Un to below 50V within 3 minutes when the power cut off.